홈페이지> 블로그> Safety requirements for hazardous chemicals warehouses

Safety requirements for hazardous chemicals warehouses

April 02, 2024


Dangerous chemical storage facilities, storage tanks and oil depots are common. Take the hazardous chemicals warehouse as an example to introduce storage facilities and their safety requirements.

1. Basic requirements for site selection

(1) Large-scale dangerous chemical warehouses and liquefied petroleum gas storage stations should be located in areas far away from residential areas, villages and towns, industrial enterprises, and important public buildings such as theaters and gymnasiums, and should choose the downwind direction that dominates the wind direction throughout the year.
(2) The production auxiliary warehouse of the factory and mining enterprise shall not be located in the residential area and public building area of ​​the city, and should be located in the safety zone at the edge of the factory.
(3) Small warehouses should be placed at the edge of the area of ​​the enterprise unit, and the requirements for fire separation should be ensured.
(4) Special warehouses for Class A and Class B goods, liquid storage tanks for Class A, B and C, and flammable material storage yards, etc., should be located in the safe area with low terrain in the urban fringe (suburb), and the city gas storage tank should be Distributed in a safe zone where users are concentrated.
(5) Liquefied petroleum gas storage tanks should be placed on the upwind side of the unit's or the region's minimum frequency wind direction for the whole year, and separate locations with good ventilation should be selected.
(6) Bottled and bottled liquids should not be placed in the open air.

2. Fire resistance rating, number of floors and building area of ​​the warehouse

(1) The fire resistance grade, number of floors and building area of ​​the dangerous chemicals warehouse shall comply with the requirements of the following table.

Table 1 Fire resistance rating, number of floors and building area of ​​the warehouse

Storage item category
fire-resistant level
Maximum number of layers allowed
Maximum allowable floor area (m2)
Single storeroom
Multi-storey warehouse
High-rise warehouse
Warehouse basement or semi-basement
Each storeroom
Firewall room
Each storeroom
Firewall room
Each storeroom
Firewall room
Firewall room
A
3, 4 items
First level
1
180
60
-
-
-
-
-
1, 2, 5, 6 items
First, second
1
750
250
-
-
-
-
-
B
1, 3, 4 items
First, second
Third level
3
1
2000
500
500
250
900
-
300
-
-
-
-
-
-
-
2, 5, 6 items
First, second
Third level
5
1
2800
900
700
300
1500
-
500
-
-
-
-
-
-
-
C
1 item
First, second
Third level
5
1
4000
1200
1000
400
2800
-
700
-
-
-
-
-
150
-
2 items
First, second
Third level
Unlimited
3
6000
2100
1500
700
4800
1200
1200
400
4000
-
1000
-
300
-
Ding
First, second
Third level
Level four
Unlimited
3
1
Unlimited
3000
2100
3000
1000
700
Unlimited
1500
-
1500
500
-
4800
-
-
1200
-
-
500
-
-
E
First, second
Third level
Level four
Unlimited
3
1
Unlimited
3000
2100
Unlimited
1000
700
Unlimited
2100
-
2000
700
-
6000
-
-
1500
-
-
1000
-
-

Note: 1 The fire resistance rating of high-rise warehouses, elevated warehouses and silos should not be lower than Grade II; silos of Grade II fire-resistant grades can be used. Warehouses storing special valuables should have a fire resistance rating of one.
2 independently constructed ammonium nitrate warehouse, calcium carbide warehouse, polyethylene warehouse, urea warehouse, coal storage warehouse and transit warehouses in stations, terminals and airports, the construction area can be increased by 1.00 times according to the provisions of this table, but the fire resistance level should not Less than two.
3 The warehouse area with automatic fire-fighting equipment can be increased by 1.00 times according to the requirements of this table and Note 2.
4 The area of ​​the barreled oil product warehouse in the oil depot can be implemented according to the current national standard “Code of Design for Petroleum Reservoirs”.
The maximum allowable building area of ​​the 5 coal homogenization warehouse fire compartment can be 12000m2, but the fire resistance rating should not be lower than the second grade.

(2) For the cold storage of the first and second grade fire-resistant grades, the maximum allowable construction area and fire separation area of ​​each warehouse shall be implemented in accordance with the relevant provisions of the Code for Design of Cold Storage.

(3) In the same warehouse or the same firewall room, if several items with different fire hazards are stored, the minimum fire resistance level, the maximum allowable number of floors and the maximum allowable building area of ​​the warehouse or compartment shall be based on the fire risk. The most sexually important item is determined.

문의하기

Author:

Mr. KUI ZHAO

이메일:

volkskychem@163.com

Phone/WhatsApp:

+8613921219871

인기 상품
You may also like
Related Categories

이 업체에게 이메일로 보내기

제목:
이메일:
메시지:

Your message must be betwwen 20-8000 characters

문의하기

Author:

Mr. KUI ZHAO

이메일:

volkskychem@163.com

Phone/WhatsApp:

+8613921219871

인기 상품
We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

송신